Technical Specifications
Item | Specification |
---|---|
Model | AAI543-H60 |
Output Channels | 16 channels, isolated |
Signal Type | 4 to 20 mA current output |
Redundancy Support | Fast switch-over response in dual-redundant configuration |
Withstanding Voltage | 1500 V AC between output and system, for 1 minute |
Allowable Load Resistance | 0 to 750 Ω |
Circuit-Open Detection | Triggered at < 0.65 mA |
Accuracy | ±48 µA |
Data Update Period | 10 ms |
Output Step Response Time | Max 40 ms |
Temperature Drift | ±16 µA per 10°C |
Maximum Power Consumption | 230 mA (5 V DC), 540 mA (24 V DC) |
HART Communication | Supported (EB401 firmware rev.2 or later required on ER bus node units) |
External Connection | Pressure clamp terminal, MIL connector cable, KS1 dedicated cable |
Dimensions (H × W × D) | 107.5 × 32.8 × 130 mm |
Weight | 0.4 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What is the primary function of the AAI543-H60 module?
A1: The AAI543-H60 is a 16-channel isolated analog output module that converts digital output values from a controller into 4 to 20 mA analog current signals for field device actuation.
Q2: Can this module be used in redundant configurations?
A2: Yes, it supports fast switch-over in dual-redundant configurations, minimizing output signal drop during module failover.
Q3: Is the AAI543-H60 compatible with HART communication?
A3: Yes, it supports HART communication when installed in an ER bus node unit with EB401 firmware revision 2 or later.
Q4: What is the maximum permissible load resistance for the output channels?
A4: Each channel supports a load resistance ranging from 0 to 750 Ω.
Q5: What type of isolation is provided by this module?
A5: The outputs are electrically isolated from the system side, withstanding up to 1500 V AC for one minute.
Q6: How accurate is the output current signal?
A6: The module offers an output accuracy of ±48 µA under standard operating conditions.
Q7: What happens to the output signal during a switch-over in a redundant setup?
A7: In fast switch-over mode, the output signal may briefly drop below 4 mA for a maximum of 2 ms during a transition.
Q8: What are the supported methods for connecting this module to field wiring?
A8: It supports pressure clamp terminals, MIL connectors, and dedicated KS1 cables for flexible installation.