Technical Specifications
Item | Specification |
---|---|
Model | AAI543-H50 |
Output Channels | 16 isolated channels |
Output Signal | 4 to 20 mA DC |
Load Resistance Range | 0 to 750 Ω |
Circuit Open Detection | Less than 0.65 mA |
Accuracy | ±48 µA |
Data Update Period | 10 ms |
Temperature Drift | ±16 µA/10 °C |
Withstanding Voltage | 1500 V AC between output and system, for 1 minute |
Current Consumption (Max.) | 230 mA (5 V DC), 540 mA (24 V DC) |
HART Communication | Supported (up to 16 devices/module; max 32 HART variables/module) |
Switch-over Response | Standard type (max. 100 ms) |
External Connection | Pressure clamp terminal, MIL connector cable, or dedicated cable (KS1) |
Dimensions (H × W × D) | 107.5 × 32.8 × 130 mm |
Weight | 0.4 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of signal does the AAI543-H50 output?
A1: It outputs a standard 4 to 20 mA DC analog signal across all 16 channels.
Q2: Is this module isolated?
A2: Yes, the AAI543-H50 provides full galvanic isolation between the output channels and the system.
Q3: Can the module detect an open loop in the circuit?
A3: Yes, it includes circuit-open detection functionality with a threshold of less than 0.65 mA.
Q4: What is the accuracy of the output signal?
A4: The output signal accuracy is ±48 µA, ensuring reliable analog transmission.
Q5: Does the AAI543-H50 support HART communication?
A5: Yes, it supports HART protocol. Up to 16 HART-compatible field devices can be connected per module.
Q6: What kind of wiring interfaces are available?
A6: The module allows connections via pressure clamp terminal blocks, MIL connectors, or dedicated KS1 cables.
Q7: What is the switching behavior in redundant configurations?
A7: In standard switch-over configuration, the output may drop below 4 mA for a maximum of 100 ms during the transition.
Q8: Is the module suitable for use in environments with temperature fluctuations?
A8: Yes, the module is designed to operate with a temperature drift of ±16 µA per 10 °C, ensuring consistent performance across typical industrial environments.