Product Parameters
Parameter | Value |
---|---|
Dimensions | 103.9 × 40.3 × 250 mm |
Weight | 0.65 kg |
Input Voltage | 115 V AC (93–132 V, 47–63 Hz) / 230 V AC (170–276 V) |
Input Current | 1300 mA (115 V) / 750 mA (230 V) |
Inrush Current | 38 A (115 V) / 19 A (230 V) |
Rated Power | 130 VA |
Output Voltage | 5.1 V DC |
Output Current | 11 A (standalone, 60°C) / 20 A (summable, 60°C) |
Fuse Rating | 2 A, slow-blow |
Harmonic Distortion | ≤10% of fundamental RMS |
Overvoltage/Overload Protection | Internal |
Power Dissipation | 6 W + (1.5 × Iout) |
Alarm Output | 1 NC contact, 6 A, 220 V (power supply fault) |
Local Signaling | Green LED (PWR OK) |
Certifications | CE, cUL, CSA C22.2 No 142, UL 508 |
Environmental Ratings | Conformal coating (Humiseal 1A33), IP20 |
Operating Temperature | 32–140°F (0–60°C) |
Storage Temperature | -40–185°F (-40–85°C) |
Relative Humidity | 95% (non-condensing) |
Operating Altitude | ≤16,404 ft (5,000 m) |
EMC/ESD Resistance | 4 kV contact / 8 kV air (IEC 801-2), 9.1 V/m (IEC 801-3) |
Product Introduction
The Schneider Electric 140CPS11420C is a compact, high-performance power supply module designed for industrial automation and control systems. It supports dual input voltage ranges (115 V/230 V AC) and delivers a stable 5.1 V DC output with high efficiency. Its summable configuration allows parallel operation for increased current capacity, making it ideal for demanding applications. The module features robust protection mechanisms, including internal overvoltage and overload safeguards, and complies with global safety standards (UL, CSA, CE).
Applications
- Industrial Control Panels: Powers PLCs, relays, and sensors in automation systems.
- Critical Infrastructure: Used in power distribution systems and emergency backup solutions.
- Communication Systems: Provides stable voltage for telecom equipment and data centers.
- Machinery: Integrates into CNC machines, robotics, and motor control units.
- Rail and Transportation: Deployed in signaling systems and onboard electronics.
Product Advantages
- Dual Voltage Compatibility: Supports 115 V and 230 V AC inputs for global use.
- High Power Density: Compact design (103.9 × 40.3 × 250 mm) with up to 20 A output in summable mode.
- Robust Protection: Internal overvoltage, overload, and short-circuit protection.
- Wide Temperature Range: Operates reliably in extreme conditions (0–60°C).
- Compliance: Meets UL 508, CSA, and CE standards for safety and reliability.
- Low Harmonic Distortion: ≤10% THD ensures clean power delivery.
Latest News Headlines
- Schneider Electric Enhances 140CPS11420C with Extended Temperature Tolerance for Harsh Environments
- New Firmware Update Improves Efficiency of 140CPS11420C in Summable Configurations
- Schneider’s 140CPS11420C Achieves ISO Certification for Industrial Safety
Recommended Related Models (Same Series)
Model | Input Voltage | Output | Current | Dimensions | Weight |
---|---|---|---|---|---|
140CPS11100C | 100–240 V AC | 24 V DC | 5 A | 120 × 40 × 250 mm | 0.7 kg |
140CPS21400C | 115/230 V AC | 5 V DC | 15 A | 103.9 × 40.3 × 250 mm | 0.68 kg |
140CPS53100C | 24–48 V DC | 12 V DC | 8 A | 90 × 35 × 200 mm | 0.5 kg |
140CPS22400C | 230 V AC | 5 V DC | 25 A | 120 × 45 × 300 mm | 0.85 kg |
140CPS21000C | 100–240 V AC | 48 V DC | 3 A | 100 × 40 × 220 mm | 0.6 kg |
140CPS11410C | 115/230 V AC | 5.1 V DC | 10 A | 103.9 × 40.3 × 250 mm | 0.63 kg |
140CPS53120C | 24 V DC | 24 V DC | 5 A | 90 × 35 × 200 mm | 0.52 kg |
140CPS21600C | 230 V AC | 12 V DC | 12 A | 120 × 45 × 300 mm | 0.8 kg |
140CPS11120C | 100–240 V AC | 12 V DC | 10 A | 120 × 40 × 250 mm | 0.72 kg |
140CPS53150C | 48 V DC | 5 V DC | 20 A | 90 × 35 × 200 mm | 0.55 kg |
Top 10 Schneider Electric Popular Models
Model | Type | Voltage | Current/Power | Dimensions | Weight |
---|---|---|---|---|---|
Altivar Process 630 | Variable Speed Drive | 380–480 V AC | 7.5–75 kW | 300 × 200 × 210 mm | 12 kg |
Modicon M580 PLC | Programmable Controller | 24 V DC | 2 A | 200 × 150 × 80 mm | 1.2 kg |
Acti9 iC60 Circuit Breaker | Circuit Breaker | 230–400 V AC | 6–63 A | 90 × 45 × 70 mm | 0.3 kg |
TeSys D Contactor | Contactor | 24–690 V AC | 9–150 A | 145 × 80 × 105 mm | 0.9 kg |
Harmony XB5R Push Button | HMI Interface | 24 V DC | 0.1 A | 22 × 22 × 30 mm | 0.05 kg |
PowerLogic PM800 | Power Meter | 100–480 V AC | N/A | 144 × 144 × 73 mm | 0.8 kg |
EasyPact TVS Circuit Breaker | MCCB | 240–690 V AC | 15–250 A | 200 × 100 × 90 mm | 1.5 kg |
Magelis HMI | Touchscreen Panel | 24 V DC | 2 A | 250 × 200 × 50 mm | 2.0 kg |
TeSys U Motor Starter | Motor Starter | 24–690 V AC | 0.15–22 kW | 150 × 100 × 120 mm | 1.8 kg |
Clipsal Solar Inverter | Solar Inverter | 230 V AC | 5 kW | 500 × 300 × 150 mm | 18 kg |
FAQ
FAQ (Q&A)
Q1: Is the 140CPS11420C compatible with both 115 V and 230 V AC inputs?
A1: Yes. It automatically detects and adapts to 115 V or 230 V AC inputs within specified ranges.
Q2: Can this module operate in parallel for higher current output?
A2: Yes. In summable mode, two units can deliver up to 20 A at 5.1 V DC.
Q3: What is the maximum ambient temperature for operation?
A3: 140°F (60°C). Derating may apply beyond 60°C.
Q4: Does it require external cooling?
A4: No. The module is convection-cooled but requires adequate airflow in enclosed panels.
Q5: How to replace the internal fuse?
A5: Disconnect power, remove the front cover, and replace the 2 A slow-blow fuse.
Q6: Is the output voltage adjustable?
A6: No. The 5.1 V DC output is fixed.
Q7: What certifications does this module hold?
A7: CE, cUL, CSA C22.2 No 142, and UL 508.
Q8: Can it withstand voltage spikes?
A8: Yes. It includes internal overvoltage protection up to 135% of rated voltage.
Q9: What is the warranty period?
A9: Standard Schneider warranty is 2 years, subject to terms.
Q10: How to troubleshoot a faulty PWR OK LED?
A10: Check input voltage, fuse, and load conditions. If issues persist, contact Schneider support.