Technical Specifications
Parameter | Specification |
---|---|
Product Model | CC-GAIX11 |
Function | Analog Input (GI/IS IOTA for high-level current/voltage) |
Compatible IOMs | CC-PAIH01 / CC-PAIH02 / CC-PAIX01 / CC-PAIX02 |
Input Channels | 16 (12 Single Ended, 4 Differential) |
Input Type | Voltage or current (2-wire/self-powered transmitters) |
Input Ranges | 0 to 5 V, 1 to 5 V, 0.4 to 2 V, 4-20 mA via 250 Ω |
A/D Converter Resolution | 16 bits |
Common Mode Rejection Ratio (DC–60 Hz) | 70 dB |
Common Mode Voltage | -6 to +5 V peak |
Normal Mode Rejection Ratio at 60 Hz | 19 dB |
Normal Mode Filter Response | Single-pole RC, -3 dB at 6.5 Hz |
Max Normal Mode Input | ±30 V (no damage on differential inputs) |
Crosstalk (DC–60 Hz) | -60 dB |
Input Impedance (Voltage Inputs) | >10 MΩ (powered) |
Input Scan Rate | 50 ms |
Hardware Accuracy (@23.5°C ±2°C) | ±0.075% of full scale |
Hardware Accuracy (0 to 60°C) | ±0.15% of full scale |
Field Power Conditioning | Individually protected, Class 1 Div 2 non-incendive |
Dimensions (W x H x D) | 115 x 130 x 35 mm |
Weight | 0.28 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of signals does the CC-GAIX11 support?
A1: The CC-GAIX11 supports high-level analog current and voltage signals, compatible with 4-20 mA loops or standard voltage ranges such as 0–5 V and 1–5 V.
Q2: Can the CC-GAIX11 be used in redundant configurations?
A2: Yes, the CC-GAIX11 supports redundant configurations when used with compatible IOMs like CC-PAIH02 or CC-PAIX02 and the corresponding redundant IOTA setup.
Q3: How many input channels are available on the CC-GAIX11?
A3: The IOTA provides 16 input channels, of which 12 are single-ended and 4 are differential.
Q4: What is the input scan rate for the CC-GAIX11 system?
A4: The input scan rate is 50 milliseconds, allowing timely processing of input signal data.
Q5: Is the CC-GAIX11 suitable for use in hazardous environments?
A5: Yes, it provides non-incendive field power conditioning compliant with Class 1, Division 2 hazardous area requirements.
Q6: What accuracy can be expected from this analog input module?
A6: The module achieves ±0.075% of full scale accuracy at room temperature and ±0.15% across the full operational temperature range.
Q7: Does the CC-GAIX11 require external power fusing?
A7: No, it includes internal individual current-limiting protection, eliminating the need for external fuses.
Q8: What kind of field power protection is implemented?
A8: The CC-GAIX11 uses individually protected circuits for transmitter field power, ensuring safety and reliability in industrial environments.