Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 | |||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Technical Specifications
Parameter | Specification |
---|---|
Dimensions | 20 × 190 × 128 mm |
Weight | 0.14 kg |
Safety-related Input | Proximity switches (DIN 19234), resistor-wired sensors |
Monitoring | Line short-circuit and break detection |
Switching Time | Approx. 10 ms |
Input Signal Current (0) | 0.35 ≤ IE ≤ 1.2 mA |
Input Signal Current (1) | 2.1 ≤ IE ≤ 6.0 mA |
Wire Break Signal | ≤ 0.28 mA |
Short Circuit Signal | ≥ 6.5 mA |
Line Impedance | ≤ 50 Ohm (DIN 19234) |
Line Length | ≤ 1000 m (Ø = 0.5 mm²) |
Supply Voltage (US) | 8.2 V |
Shunt Resistance (R) | 681 Ohm; 1 %; 0.25 W |
Operating Voltage | 5 V = 90 mA; 24 V = 170 mA |
Space Requirement | 4 TE |
FAQ
FAQ
-
Q: What types of sensors can be connected to the HIMA F3237 module?
-
Q: How does the F3237 module monitor sensor lines?
-
A: The module monitors for line short-circuits and wire breaks to ensure safety and proper functionality.
-
-
Q: What is the switching time of the F3237 module?
-
A: The switching time of the F3237 module is approximately 10 milliseconds.
-
-
Q: What current range does the F3237 module use for input signals?
-
A: The input signal current ranges from 0.35 mA to 1.2 mA for a “0” signal, and from 2.1 mA to 6.0 mA for a “1” signal.
-
-
Q: How does the module detect wire breaks or short circuits?
-
A: Wire breaks are detected with a signal ≤ 0.28 mA, while short circuits are detected with a signal ≥ 6.5 mA.
-
-
Q: What is the maximum allowable line length for connecting sensors?
-
A: The maximum allowable line length is 1000 meters, with a cable diameter of 0.5 mm².
-
-
Q: What is the supply voltage requirement for the F3237 module?
-
A: The F3237 module requires a supply voltage of 8.2 V.
-
-
Q: How is the F3237 module tested during operation?
-
A: The module undergoes automatic testing, including switch-on and switch-off capability, input circuit crosstalk, input filter function, and sensor line monitoring for short circuits and breaks.
-
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.