Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 | |||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Product Parameters
Parameter | Specification |
---|---|
Model Number | 3500/50-01-00 (Module), 133442-01 (I/O Module with Internal Terminals) |
Channel Count | 2 channels |
Input Types | Proximity probes or magnetic pickups |
Input Signal Range | +10.0 V to -24.0 V |
Input Impedance | 20 kΩ (standard), 40 kΩ (TMR), 7.15 kΩ (Internal Barrier) |
Power Consumption | 5.8 W (typical) |
Output (Recorder) | +4 to +20 mA (proportional to RPM) |
Recorder Load Resistance | 0 to 600 Ω |
Buffered Output Impedance | 550 Ω |
Transducer Power Supply | 24 Vdc, 40 mA max per channel |
Speed Measurement Range | 0.0039 to 255 events/rev; up to 99,999 rpm; max 20 kHz input freq |
Accuracy (RPM) | <100 rpm = ±0.1 rpm; 100–10,000 rpm = ±1 rpm; 10,000–99,999 rpm = ±0.01% |
RPM/Min Accuracy | ±20 rpm/min |
Threshold Modes | Auto (≥1 Vpp), Manual (+9.5 Vdc to -23.5 Vdc, ≥0.5 Vpp) |
Hysteresis Range | 0.2 to 2.5 V |
Alarm Setpoints | Alarm 1: 1–60 s (1 s step), Alarm 2: 1–60 s (0.1 s step) |
Compliance | FCC Part 15, EN 61000-6-2/-6-4, EN 61010-1, RoHS, DNV, ABS |
Hazardous Area Ratings | cNRTLus, ATEX/IECEx Zone 2 (with/without internal barriers) |
Dimensions (I/O Module) | 241.3 x 24.4 x 99.1 mm |
Weight (I/O Module) | 0.20 kg |
Dimensions (Monitor Module) | 241.3 x 24.4 x 241.8 mm |
Weight (Monitor Module) | 0.82 kg |
Rack Slot Requirements | 1 full-height front slot (monitor), 1 full-height rear slot (I/O) |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of signals does the 3500/50-01-00 Tachometer Module accept?
A1: It accepts signals from proximity probes or magnetic pickups, provided the input voltage is within +10.0 V to -24.0 V.
Q2: Can this module be used for overspeed protection?
A2: No, it should not be used for overspeed protection or speed control systems due to lack of redundancy and response speed.
Q3: What is the minimum signal amplitude required for triggering in manual mode?
A3: The minimum signal amplitude for manual mode is 500 millivolts peak-to-peak.
Q4: What is the speed range the module can monitor?
A4: It supports up to 99,999 rpm, with an input frequency range up to 20 kHz depending on the sensor type.
Q5: How is the RPM accuracy specified across different speed ranges?
A5: Less than 100 rpm = ±0.1 rpm; 100 to 10,000 rpm = ±1 rpm; 10,000 to 99,999 rpm = ±0.01% of actual speed.
Q6: Is the module suitable for zero speed and reverse rotation detection using magnetic pickups?
A6: No, magnetic pickups should not be used for zero speed or reverse rotation functions due to signal instability at low speeds.
Q7: Can I use external termination blocks with the internal terminal version (133442-01)?
A7: No, external termination blocks are incompatible with I/O modules that have internal terminals.
Q8: What certifications does this module comply with for hazardous areas?
A8: It meets cNRTLus and ATEX/IECEx certifications for Class I, Zone 2 or Division 2, depending on configuration.
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.