Technical Specifications
Parameter | Value |
---|---|
Product ID | 3BSE020850R1 |
Type | Redundant |
Connection | Terminal block |
Channels | 16 |
Voltage | 50 V |
Mounting | Horizontal |
Mounting Detail | 55 ºC (131 ºF) |
Max Current per I/O Channel | 3 A |
Max Current Process Connection | 10 A |
Acceptable Wire Sizes | Solid: 0.2 – 4 mm², Stranded: 0.2 – 2.5 mm², 24 – 12 AWG |
Recommended Torque | 0.5 – 0.6 Nm |
Stripping Length | 7 mm |
Dielectric Test Voltage | 500 V a.c. |
Environmental Certifications | CE, UL, ATEX, cULus, ABS, BV, DNV-GL, LR |
Temperature, Operating | 0 to +55 °C (+32 to +131 °F) |
Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
Pollution Degree | Degree 2, IEC 60664-1 |
Relative Humidity | 5 to 95 %, non-condensing |
Max Ambient Temperature | 55 °C (131 °F) |
Protection Class | IP20 (IEC 60529) |
Dimensions | Width: 131 mm, Depth: 64 mm, Height: 186.5 mm |
Weight | 0.6 kg |
FAQ
FAQs (Q&A Format)
Q1: What is the maximum number of I/O channels the ABB TU842 can handle?
A1: The ABB TU842 supports up to 16 I/O channels.
Q2: What is the maximum current rating per I/O channel?
A2: The maximum current per I/O channel is 3 A.
Q3: What is the maximum current for process connections?
A3: The maximum current for process connections is 10 A.
Q4: What are the acceptable wire sizes for the ABB TU842?
A4: For solid wires, the acceptable size is 0.2 – 4 mm², and for stranded wires, it is 0.2 – 2.5 mm², 24 – 12 AWG.
Q5: Can the ABB TU842 be mounted vertically?
A5: No, the ABB TU842 is designed for horizontal mounting.
Q6: What is the recommended torque for wiring?
A6: The recommended torque is between 0.5 and 0.6 Nm.
Q7: What environmental certifications does the ABB TU842 have?
A7: The ABB TU842 is certified with CE, UL, ATEX, cULus, ABS, BV, DNV-GL, and LR.
Q8: What are the operating temperature limits for the ABB TU842?
A8: The operating temperature range is from 0 to +55 °C (+32 to +131 °F).