Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 | |||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Technical Specifications
Parameter | Value |
---|---|
Product Type | Digital Output Module |
Number of Outputs | 32 |
Number of Groups | 4 groups of 8 outputs |
Output Logic | Positive Logic (Source) |
Addressing Requirement | 2 output words |
Output Voltage | 24 V DC |
Output Voltage Range | 19.2…30 V |
Maximum Output Voltage | 56 V (1.3 s decaying pulse) |
Maximum Voltage Drop | < 0.4 V at 0.5 A |
Maximum Load Current | 16 A per module, 4 A per group |
Surge Current | 5 A, 0.0005 s |
Response Time | <= 1 ms for 0 to 1 state |
<= 1 ms for 1 to 0 state | |
Maximum Leakage Current | 0.4 mA at 30 V |
Load Inductance | Inductance(H) = 0.5 / (current(A))² x (switching frequency(Hz)) 50 Hz |
Fault Indication | Blown fuse |
Loss of field power | |
Associated Fuse Rating | 3 A per point, 5 A per group |
Channel to Bus Isolation | 1780 Vrms DC (1 minute) |
Group Isolation | 500 Vrms DC (1 minute) |
Protection Type | Internal output protection by 5 A fuse per group |
Power Dissipation | 1.75 W + (0.4 V x total module load current) |
Marking | CE |
Local Signaling | Bus communication (Active) 1 LED (green) |
External fault (F) 1 LED (red) | |
Input status 32 LEDs (green) | |
Bus Current Requirement | 330 mA |
Module Format | Standard |
Net Weight | 0.45 kg |
Dimensions | 103.9 × 40.3 × 250 mm |
Environmental Conditions | Certifications: GOST, BV, RMRS, ABS, DNV, GL, RINA, C-tick, FM Class 1 Division 2 |
Standards | UL 508, CSA C22.2 No 142 |
ESD Resistance | IEC 801-2: 4 kV contact, 8 kV air |
EMF Resistance | IEC 801-3: 9.1 V/m (80…2000 MHz) |
Operating Temperature Range | 0…60 °C (32…140 °F) |
Storage Temperature Range | -40…85 °C (-40…185 °F) |
Relative Humidity | 95% without condensation |
Operating Altitude | <= 5000 m (16404.2 ft) |
FAQ
FAQ
-
Q: What is the output voltage range of the Schneider 140DDO35300 Discrete Output Module?
-
A: The output voltage range is 19.2 V to 30 V.
-
-
Q: What is the maximum load current for this module?
-
A: The maximum load current per module is 16 A, and 4 A per group.
-
-
Q: What is the response time of the module?
-
A: The response time is less than or equal to 1 ms for both state 0 to state 1 and state 1 to state 0.
-
-
Q: What is the maximum surge current for this module?
-
A: The maximum surge current is 5 A for 0.0005 seconds.
-
-
Q: What is the formula for the load inductance?
-
A: The formula for load inductance is Inductance(H) = 0.5 / (current(A))² x (switching frequency(Hz)) at 50 Hz.
-
-
Q: Does this module have fault indication lights?
-
A: Yes, the module has several indication lights: a green LED for bus communication, a red LED for external fault detection, and 32 green LEDs for input status.
-
-
Q: What is the operating temperature range of this module?
-
A: The operating temperature range is 0°C to 60°C (32°F to 140°F).
-
-
Q: What is the net weight of the module?
-
A: The net weight of the module is 0.45 kg.
-
Tags
Packing & Delivery
We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.
For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.
Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.