Technical Specifications
Parameter | Description |
---|---|
Module Type | DI802 3BSE022360R1 |
Module Function | Digital Input, Current Sinking |
Number of Channels | 8 individually isolated channels |
Rated Voltage | 120 V AC (77–130 V AC); 110 V DC (75–145 V DC) |
Input Voltage Range “1” | 77–130 V AC; 75–145 V DC |
Input Voltage Range “0” | 0–30 V AC; 0–20 V DC |
Nominal Input Current | 10 mA @ 120 V AC; 2.8 mA @ 110 V DC |
Input Impedance | 12 kΩ (AC); 39 kΩ (DC) |
Input Frequency (AC) | 47–63 Hz |
Digital Filter Times | Selectable: 2, 4, 8, 16 ms |
Analog Filter Delay | On/Off delay: 5 ms / 18 ms |
Voltage Supervision | Channel 8 supervises channels 1–7 |
Current Consumption | 50 mA (5 V via ModuleBus) |
Max Cable Length | 200 m (AC); 600 m (DC) |
Protection Rating | IP20 (IEC 60529) |
Mounting Method | DIN rail with locking mechanism |
Channel Isolation | Individually galvanically isolated |
Dielectric Test Voltage | 2000 V AC |
Recommended Wire Strip | 6–7.5 mm |
Terminal Torque | 0.5–0.6 Nm |
Acceptable Wire Sizes | Solid: 0.05–2.5 mm²; Stranded: 0.05–1.5 mm² (30–12 AWG) |
Dimensions (H×W×D) | 110 × 86.1 × 58.5 mm |
Weight | 0.24 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of signals does the DI802 module accept?
A1: The module supports 120 V AC or 110 V DC digital input signals, using a current sinking configuration.
Q2: Are the input channels electrically isolated?
A2: Yes, all 8 channels are individually isolated to enhance system safety and reliability.
Q3: What is the function of channel 8?
A3: Channel 8 can be used to monitor field power voltage for channels 1 to 7.
Q4: Does the module offer input signal filtering?
A4: Yes, digital filtering is available with selectable delay times of 2, 4, 8, and 16 ms.
Q5: How is the module installed?
A5: The module is DIN rail mountable with an integrated locking mechanism.
Q6: What are the acceptable wiring specifications?
A6: Solid wires: 0.05–2.5 mm², Stranded wires: 0.05–1.5 mm², Strip length: 6–7.5 mm.
Q7: What is the insulation voltage of the DI802?
A7: The rated insulation voltage is 250 V, and dielectric test voltage is 2000 V AC.
Q8: In which industrial environments is DI802 suitable?
A8: It is suitable for high-voltage input monitoring in industrial automation systems requiring high reliability and voltage supervision.