Yokogawa AAI543-H00/K4A00 Analog Output Module

Yokogawa AAI543-H00/K4A00 Analog Output Module

Manufacturer:Yokogawa

Product Number:AAI543-H00/K4A00

Product Type:Analog Output Module

Origin:Japan

Dimensions:107.5 × 32.8 × 130 mm

Weight:0.4 kg

Views:1

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/04/AAI543-H00-K4A00-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/AAI543-H00-K4A00-2.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/AAI543-H00-K4A00-3.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/AAI543-H00-K4A00-4.jpg
Company Information
E-mail [email protected]
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393
Add Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China

Technical Specifications

Item Specification
Model AAI543-H00/K4A00
Output Channels 16 isolated channels
Output Signal 4 to 20 mA DC
Withstanding Voltage 1500 V AC (between output and system, for 1 minute)
Allowable Load Resistance 0 to 750 Ω
Circuit-Open Detection < 0.65 mA
Accuracy ±48 µA
Data Update Period 10 ms
Ambient Temperature Drift ±16 µA / 10 °C
Maximum Current Consumption 230 mA (5 V DC), 540 mA (24 V DC)
HART Communication Available (when installed in ER node with EB401 firmware rev. 2 or later)
External Connection Pressure clamp terminal, MIL connector cable, or KS1 dedicated cable
Dimensions (W x D x H) 107.5 × 32.8 × 130 mm
Weight 0.4 kg
Redundancy Support Dual-redundant (standard or fast switch-over response)
FAQ

Frequently Asked Questions (FAQ)

Q1: What is the output type supported by the AAI543-H00/K4A00 module?
A1: The module provides 16 channels of 4 to 20 mA DC analog current output.

Q2: Is the AAI543 module capable of HART communication?
A2: Yes, the H00 variant supports HART communication when installed in a compatible ER bus node unit with EB401 firmware rev. 2 or later.

Q3: Can the AAI543 be used in a dual-redundant configuration?
A3: Yes, it supports dual-redundant configurations with either standard or fast switch-over response depending on the model suffix.

Q4: What type of isolation is provided in this module?
A4: Isolation is provided between the output channels and the system, rated at 1500 V AC for 1 minute.

Q5: What is the load resistance range supported?
A5: The module supports an allowable load resistance between 0 and 750 Ω per output channel.

Q6: How often is the data refreshed in the module?
A6: The data update period is 10 milliseconds.

Q7: What happens if an output circuit is open?
A7: The module detects a circuit-open condition when the current drops below 0.65 mA.

Q8: What cabling options are available for connecting the module?
A8: The AAI543-H00/K4A00 can be connected using pressure clamp terminals, MIL connectors, or the KS1 dedicated cable.