Welcome to TilGames!

GE IC660BBD025V Mark II Series DC 32-Circuit Source/Sink I/O Module

GE IC660BBD025V Mark II Series DC 32-Circuit Source/Sink I/O Module

Manufacturer:GE Fanuc

Product Number:IC660BBD025V

Product Type:I/O Module

Origin:USA

Dimensions:90.5 × 44.2 × 119.38 mm

Weight:1.8 kg

Views:10

Payment Methods:T/T, PayPal, Western Union

Condition:New & In Stock

Shipping Port:Xiamen, China

Warranty:1 Year

Lead Time:1-3 Working Days

Certificate:COO

Courier partners:DHL, UPS, TNT, FedEx and EMS.

Business hours:7*24

Send Inquiry
Description
FAQ
Products Description
https://www.tilgames.com/wp-content/uploads/2025/04/IC660BBD025V-1.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/IC660BBD025V-2.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/IC660BBD025V-3.jpg
https://www.tilgames.com/wp-content/uploads/2025/04/IC660BBD025V-4.jpg
Company Information
E-mail [email protected]
Mobile +8613666033393
Whatsapp +8613666033393
WeChat 13666033393
Add Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China

Technical Specifications

Parameter Details
Model IC660BBD025V
Series Genius Block Mark II Series
Circuit Configuration 32 configurable circuits (input/output/output with feedback)
Operating Voltage 5 VDC (TTL compatible), 12/24 VDC
Voltage Range 4.9–5.3 VDC (5 V supply), 10–30 VDC (12/24 V supply)
Input ON Levels 8–12 VDC (12V supply), 18–24 VDC (24V supply)
Input OFF Levels 0–6 VDC (12V supply), 0–12 VDC (24V supply)
Input Impedance (Typical) 3.3 kΩ
Selectable Input Filter Times 1–100 ms in 15 increments
Input Processing Time (Typical) 1.4 ms + filter delay
Output Type Sink type
Maximum Output Current (per circuit) 0.5 A steady-state
Maximum Inrush Current 4 A for 10 ms (max once per 0.5 sec)
Total Block Output Current 16 A
Output OFF Leakage Current 10 µA max
Output Turn-On Delay 0.5 ms max
Output Voltage Drop 2.0 V max at 4 A inrush
Protection Self-resetting short circuit protection, surge handling
Diagnostics Failed switch detection, switch-state mismatch, overload detection
LED Indicators Unit OK, I/O Enabled, individual logic-side indicators
Isolation (Block-to-Block) 850 V
Heat Dissipation 11 W (min, with 8 inputs), 18 W (max, with 32 outputs @ 0.5 A)
Power Requirements 150 mA typical / 300 mA max
Power Supply Dropout Time 4 ms @ 12 V, 20 ms @ 24 V
Environmental Temperature Operating: 0 to +60°C, Storage: -40 to +100°C
Humidity 5% to 95% non-condensing
Vibration 5–10 Hz: 0.2″ displacement; 10–200 Hz: 1G
Dimensions (H × W × D) 90.5 mm × 44.2 mm × 119.38 mm
Weight 1.8 kg
Compatible Monitor Hand-held Monitor IC660HHM501
FAQ

Frequently Asked Questions (FAQ)

Q1: What type of devices can be connected to the IC660BBD025V block?
A1: It supports both 2-wire and 3-wire proximity switches for inputs and low-power output devices such as relays, lamps, and contactors.

Q2: Can this block be configured for both input and output use on the same unit?
A2: Yes, each of the 32 circuits can be independently configured as an input, output, or output with feedback.

Q3: Is the IC660BBD025V compatible with 5V TTL logic levels?
A3: Yes, it is TTL-compatible and can operate properly with a 5V DC supply in addition to 12V and 24V levels.

Q4: What is the recommended method for resetting a faulted output circuit?
A4: To reset a failed circuit due to an overload, either cycle the block’s power or issue a “CLEAR FAULTS” command from a handheld monitor or bus controller.

Q5: How is short circuit protection handled by this I/O block?
A5: Each circuit includes a self-resetting protection feature that shuts off the output if current exceeds 5A for more than 1 ms.

Q6: How are the operating states indicated on the unit?
A6: The block uses a combination of unit-level and per-circuit LEDs to indicate status, faults, forced states, and communication health.

Q7: What environmental conditions must be maintained for safe operation?
A7: The block should operate within 0°C to +60°C and be housed in a clean, dry enclosure with sufficient airflow.

Q8: Is the IC660BBD025V block suitable for use in redundant or duplex systems?
A8: Yes, it supports various redundancy modes including standby, duplex, and GMR, which can be configured via handheld monitor or bus controller.

Tags
Packing & Delivery

We will use wear-resistant cartons to seal the boxes, and take photos for your confirmation before sealing. We will pack the boxes only after confirmation.

For express delivery, we will use DHL, UPS, TNT, FedEx and EMS.

Please rest assured that we have a deep cooperation with express delivery companies and can ensure that your goods are delivered to you in good condition.


Leave Your Message


Leave a message