Products Description




Company Information | |||
[email protected] | |||
Mobile | +8613666033393 | ||
+8613666033393 | |||
13666033393 | |||
Add | Room 1004, No. 62 Xiangxiu Li, Siming District, Xiamen City, Fujian Province, China |
Technical Specifications and Features
Attribute | Description |
---|---|
Model | IC694MDL660-EC |
System | RX3i PACSystems |
Input Type | Discrete Input (Positive/Negative Logic) |
Input Voltage (Nominal) | 24 VDC |
Input Voltage Range | 0 to 30 VDC |
Number of Inputs | 32 (arranged in four isolated groups of 8 inputs each) |
Input Current per Point | 7.0 mA typical at 24 VDC |
Input Voltage Thresholds | ON-State: 11.5–30 VDC, OFF-State: 0–5 VDC |
Input Current Thresholds | ON-State: ≥ 3.2 mA, OFF-State: ≤ 1.1 mA |
Input Filter Times | Selectable: 0.5 ms, 1.0 ms, 2.0 ms, 5 ms, 10 ms, 50 ms, 100 ms |
Isolation (Field to Backplane) | 250 VAC continuous, 1500 VAC for 1 minute (optical) |
Isolation (Group to Group) | 250 VAC continuous, 1500 VAC for 1 minute |
Diagnostics | Terminal block presence detection; status reported to RX3i CPU |
LED Indicators | 32 green LEDs (individual channel status), 1 TB LED (red/green for TB lock) |
Filter Configuration | Set via output data references in RX3i CPU programming |
Power Consumption | 300 mA from 5V backplane (all inputs ON) |
Module Identification Code | 0x058h |
Supported Terminal Blocks | Box-style: IC694TBB032, Spring-style: IC694TBS032 (ordered separately) |
Backplane Compatibility | RX3i series only (CPU version 2.90 or later), not compatible with Series 90-30 |
Mounting | Any I/O slot in RX3i system |
Dimensions (W x H x D) | 34 mm x 145 mm x 140 mm |
Weight | 0.91 kg |
FAQ
Frequently Asked Questions (FAQ)
Q1: What type of input signals does the IC694MDL660-EC support?
A1: It supports 24 VDC discrete input signals with both positive and negative logic configurations.
Q2: Can this module be used with Series 90-30 PLCs?
A2: No, it is only compatible with RX3i PACSystems and requires CPU firmware version 2.90 or higher.
Q3: How many input channels does the module provide?
A3: The module provides 32 discrete inputs, divided into four groups of 8 channels, each group electrically isolated.
Q4: What are the selectable filter times available for input signal conditioning?
A4: The module supports filter times of 0.5 ms, 1.0 ms, 2.0 ms, 5 ms, 10 ms, 50 ms, and 100 ms.
Q5: Does the IC694MDL660-EC provide any built-in diagnostic functions?
A5: Yes, it detects the presence of the terminal block and reports this status to the RX3i CPU.
Q6: What happens if the firmware of the module becomes corrupted or is missing?
A6: All LEDs will be off, and while the CPU may still scan the module, it may not generate a fault. It’s recommended not to rely solely on diagnostic messages.
Q7: What is the significance of the TB LED color on the module?
A7: The TB LED is green when the terminal block is properly locked in place and red when it is not secured.
Q8: What kind of isolation does this module offer?
A8: It offers optical isolation between the field and backplane (250 VAC continuous), and between input groups (250 VAC continuous), withstanding up to 1500 VAC for one minute.